1. Overview

YB□-12 (ZBW-12) series prefabricated substation is a compact complete set of power distribution equipment that combines high-voltage electrical equipment, transformers, low-voltage electrical equipment, etc. It is used in urban high-rise buildings, urban and rural buildings, luxury villas, square parks, residential areas, high-tech development zones, small and medium-sized factories, mines and oil fields, and temporary construction power supply places to receive and distribute electrical energy in the power distribution system.

The YB-12 series prefabricated substation produced by our company is a new product that integrates the advantages of similar products at home and abroad and is improved and enhanced. It has the characteristics of strong completeness, small size, compact structure, safe and reliable operation, convenient maintenance, and mobility. Compared with conventional civil construction substations, the floor area of ​​box-type substations with the same capacity is usually only 1/10-1/5 of that of conventional substations, which greatly reduces the design workload and construction workload, and reduces construction costs. In the power distribution system, it can be used for ring network distribution systems, dual power supply or radiation terminal distribution systems, and is a new set of equipment for the construction and transformation of urban and rural substations.

2. Main technical parameters

2.1 Rated voltage

High-voltage side rated voltage: 3, 6, 10, 20, 35kV

High-voltage side maximum operating voltage: 3.6, 7.2, 12, 24, 40.5kV

Low-voltage side rated voltage: 0.4kV

Mechanism opening and closing and auxiliary circuit rated voltage: AC, 100, 220, 380V

2.2 rated current

Low-voltage side rated voltage: 0.4kV

style="line-height:2;">High-pressure circuit 10, 12.5, 20, 25, 31.5, 40, 50, 63, 80, 100, 125, 160, 200, 250, 315, 400, 630, 800, 1000, 1250A

 

Low-pressure circuit: 40, 50, 63, 100, 200, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000, 2500, 3150, 4000A

2.3 Transformer rated capacity

50, 100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000, 2500kVA Note: 1600kVA and above require special non-standard design.

2.4 Rated frequency: 50Hz

2.5 Box transformer housing protection level

Indoor: Each room shall not be less than IP2XDH

Outdoor: Each room shall not be less than IP33DH

2.6 Box transformer high voltage side wiring method:

Single-end power supply, double-end power supply, ring network power supply

2.7 Box transformer noise level

Internal dry-type transformer ≤65dB

Built-in oil-immersed transformer ≤55dB

 