1. Product Overview
EGSK-12 is a new generation of green and environmentally friendly AC metal-enclosed gas-insulated switchgear developed according to the needs of today's power grid. It is fully suitable for public and industrial distribution networks, infrastructure projects, rail transit, metallurgy, petrochemicals, docks, ships, drilling platforms and other fields. It is used to receive and distribute electric energy and control, protect and monitor circuits.
2. Technical Parameters
| Rated insulation level |
project |
unit |
parameter |
| Rated voltage |
kV
|
12
|
| Rated frequency |
Hz
|
50
|
| Insulation medium |
kV
|
N2
|
| lmin power frequency withstand voltage (zero gauge pressure) |
42
|
| Lightning impulse withstand voltage (zero gauge pressure) |
75
|
| Auxiliary circuit 1min power frequency withstand voltage |
2
|
| Partial discharge (1.1 times rated voltage) |
pC
|
≤10
|
| Rated current |
A
|
≤3150
|
| Rated short-circuit breaking current |
kA
|
≤40
|
| Rated short-circuit making current |
kA
|
≤100
|
| Rated short-time withstand current (4S) |
kA
|
≤40
|
| Rated peak withstand current |
kA
|
≤100
|
| Switching single/back-to-back capacitor bank current |
A
|
630/400
|
| Rated cable charging breaking current |
A
|
25
|
| Circuit breaker electrical life |
Second-rate |
50
|
| Circuit breaker mechanical life |
Second-rate |
10000~30000(depending on rated current) |
| Mechanical life of disconnectors and earthing switches |
Second-rate |
3000
|
| Internal arc level |
kA/s
|
IACA FLR31.5kA/0.5s,25kA/ls
|
| Temperature rise test (zero gauge pressure) |
/
|
l.llr
|
| Rated operating cycle |
/
|
O-0.3s-CO-180s-CO
|
| Rated inflation pressure (relative) |
MPa
|
0.02
|
| Alarm pressure (relative) |
MPa
|
0.01
|
| Minimum working pressure (relative) |
MPa
|
0
|
| Annual leakage rate |
%/Y
|
<0.05
|
| Protection level |
/
|
Air box: IP65; others: IP4X |